Qty 2 2008 925 KW (1.8 MW Total) Caterpillar G3516 1200 RPM 480 Volts Landfill Gas

Caterpillar GenSets

Manufacturer
Caterpillar
GIBUYS Item No
MR1105
Availability Out of stock
$109,900.00

We offer a variety of finance programs including no payment for 90 days and a cash loan to any equipment financing. CIT is our trusted partner for your financing needs.

LEARN MORE APPLY NOW

Buy with confidence

All of our products carry a 100% satisfaction guarantee.

We offer a 30-day return policy on everything we sell unless otherwise noted. We care about our customers and we strive for 100% satisfaction with every order.
Product Description

Green Industrial is selling this complete generator package. Includes 2 Caterpillar G3516 925KW Continuous Duty 1200 RPM Generator sets, 2 IEA Remote Radiators, and Caterpillar Paralleling Switchgear. Unison Landfill gas conditioning skid is also available. These generators are running take out machines that are due for an overhaul.

FOB: Belgium, Wisconsin 53004 USA

Condition: Running Take Out Generators
Additional Information on condition below. An inspection and report by Caterpillar Dealer.

Generator Package Specifications:
Qty: 2 of each

Manufacturer: Caterpillar
YEAR: 2008
KW Rating: 925 KW, Continuous Duty
KVA Rating: 1156 KVA, Continuous Duty
RPM: 1200
Voltage: 480 Volts Wye, Series
Phase: 3
Hertz: 60
Amperage: 1391
Maximum Temp rise: 105 Degrees C
Class H Insulation
Generator Model SR4 B
Generator Arrangement Number: 158-6415 (Stamped) 158-6416 (Nameplate)
Generator Serial Numbers: Unit 1: 9GZ00628
Unit 2: 9GZ00629

ENGINE SPECIFICATIONS:

Manufacturer: Caterpillar
YEAR: 2008
Engine Model: G3516
Arrangement Number: 165-6135
Engine Serial Numbers: Unit 1 4EK05255
Unit 2 4EK05256
HOURS: Unit 1 : 45,679 Total (11,976 since In Frame Overhaul in 2014)
Unit 2 : 55,447 Total (23,570 since In Frame Overhaul in 2014)
Engine RPM: 1200
Fuel: Landfill Gas / Natural Gas (Set to run landfill gas)

Switchgear:
Caterpillar / Eaton Cutler Hammer ISO Paralleling Switchgear
3200 Amp Rated Switchgear
3 Phase, 4 Wire
Short Circuit Rating: 100 KA
Each generator has a 1600 Amp Circuit Breaker

Remote Radiators:
Qty: 2
Manufacturer: IEA
HCR-M84-03-24-S10
Serial# 16714-1
16714-2
Year: 2008

CONDITION REPORT conducted by Caterpillar Dealer:

UNIT1: Engine Serial# 4EK05255 HOUR Reading: 45,679

Engine had an in-frame overhaul on 6/30/2014, 33703 engine hours. All preventative maintenance has been performed per Caterpillar Operation & maintenance manual to include oil samples every 125 hours of operation. A major overhaul was due at 40,000 hours of operation, but has not been performed yet at the customer's request. There are currently 11,976 hours on the engine since the in-frame overhaul, Caterpillar recommends top end overhaul every 8000 hours or replacement if valve recession readings determine cylinder head is due to fail.

This engine at this time requires a major overhaul be performed and the generator be removed, tested & cleaned. New generator bearings are also required.

UNIT2: Engine Serial# 4EK05256 HOUR Reading: 55,447

Engine had an in-frame overhaul on 6/18/2014, 31877 engine hours. All preventative maintenance has been performed per Caterpillar Operation & maintenance manual to include oil samples every 125 hours of operation. A major overhaul was due at 40,000 hours of operation, but has not been performed yet at the customer's request. There are currently 23,570 hours on the engine since the in-frame overhaul, Caterpillar recommends top end overhaul every 8000 hours or replacement if valve recession readings determine cylinder head is due to fail. Cylinder heads 12,13,14, and 16 were replaced on 1/3/18 w 48,460 hours. Cylinder heads 1,2,3,5,7,9, and 15 were replaced on 3/1/18 w 49,330 hours.

This engine at this time requires a major overhaul be performed and the generator be removed, tested & cleaned. New generator bearings are also required.

Remote IEA Radiators: Both radiators are in good working order with no leaks or other known defects.

Caterpillar ISo Switchgear: Serial# SWG36015
Switchgear is operational with no known defects EXCEPT one of the HMI screens does not light up.